Resources

NFPA 10 Fire Extinguisher Inspection: The Complete Contractor's Reference

5-Minute Read
February 16, 2026
Example H2
Example H3
Example H4
Example H5
Example H6
Share Article

You just landed a new hospital contract. Forty-seven buildings across three campuses, and the facilities director hands you a spreadsheet with 612 extinguishers on it. Half are ABC dry chemical. There are CO2 units in the server rooms, Class K in the cafeteria kitchens, clean agent in the telecom closets, and a handful of water mist units scattered through the surgical suites. Every single one is on a different maintenance timeline based on its manufacture date.

Welcome to NFPA 10 fire extinguisher inspection management at scale.

NFPA 10 is the standard that governs portable fire extinguisher selection, installation, inspection, maintenance, and testing. While it's one of the more straightforward NFPA codes on paper, managing compliance across hundreds or thousands of units for multiple clients is where things get complicated. If you're running a fire protection business and extinguishers are part of your service mix, this is the reference guide you'll want bookmarked.

What NFPA 10 Actually Requires

The current widely adopted edition is NFPA 10, 2022, which updated visibility and signage requirements, reorganized the selection chapter, and refined hydrostatic testing definitions. The 2026 edition is already available and introduces performance-based inspection programs that can adjust inspection frequency, plus new condemned-extinguisher disposal requirements.

Here's what trips up a lot of contractors: Section 7.1.1 puts the responsibility for ITM on the building owner, not on you. But you're the one performing the certified work, and your name is on the service tag. So when the AHJ shows up and finds an expired extinguisher, guess whose phone rings first.

The ITM requirements live in Chapter 7 (inspection, maintenance, and recharging) and Chapter 8 (hydrostatic testing). Annex I contains the detailed step-by-step maintenance procedures your technicians should be following in the field.

Monthly Visual Inspections: Simple but Constantly Missed

Monthly inspections are required at minimum every 30 days per Section 7.2.1. Building staff can handle these without certification. The problem is they often don't.

The monthly checklist covers ten specific items: the extinguisher is in its designated location, it's visible or has directional signage, access isn't blocked, the pressure gauge reads in the operable range, the unit feels full when hefted or weighed, safety seals and tamper indicators are intact, there's no obvious physical damage or corrosion or leakage or clogged nozzle, operating instructions are legible and facing outward, and wheeled units have tires, wheels, hoses, and nozzles in good shape. For non-rechargeable units, the push-to-test indicator also gets checked.

One thing worth mentioning to your customers: a gauge reading in the green zone doesn't guarantee the extinguisher will work. A broken seal might indicate a partial discharge too small to move the needle. That's why the tamper indicator check matters just as much as the gauge reading.

Documentation requires a date and inspector initials on a tag, a checklist kept on file, or an electronic record. Electronic monitoring systems are also permitted as an alternative to manual monthly inspections.

Annual Maintenance and the Internal Examination Trap

Annual maintenance must be performed by a trained, certified technician with proper tools and the manufacturer's service manual. This goes beyond visual checks. You're doing a thorough external examination, verifying operating instructions and HMIS labels, examining mechanical parts, checking the extinguishing agent, and confirming the expelling means. New tamper seals go on after service, and the service tag must show month and year, technician name, and company.

Here's where contractors get burned: internal examination during annual maintenance is required for some types but not all. Cartridge-operated extinguishers get opened every year. Stored-pressure loaded-stream and antifreeze extinguishers also need annual internal exams. But your standard stored-pressure ABC dry chemical? That's on a 6-year internal exam cycle. CO2 and non-rechargeable types don't get annual internals either.

What most contractors miss is the varying internal exam intervals for other types. AFFF and FFFP foam extinguishers need internals every 3 years. Water, water mist, CO2, wet chemical, and stainless-steel dry chemical units need them every 5 years. If you're servicing a restaurant chain with Class K units in every kitchen, those wet chemical extinguishers are on a 5-year internal exam and 5-year hydrostatic test cycle, not the 12-year cycle most people default to in their heads.

A replacement extinguisher of equal rating is required during service per Section 7.1.3. Your technician can't just pull a unit and leave the customer unprotected.

The 6-Year and 12-Year Problem

The 6-year internal examination applies to stored-pressure extinguishers that are on a 12-year hydrostatic cycle, primarily ABC and BC dry chemical, clean agents like Halotron and FE-36, and Class D dry powder units. The extinguisher gets emptied, all internal components and agent inspected per the manufacturer's manual, parts replaced as needed, then recharged and recertified. A verification-of-service collar must be installed around the neck afterward.

The 12-year hydrostatic test is the big one. But not all extinguishers follow that 12-year cycle, and this is the detail that creates the most scheduling headaches. Water-based units (water, AFFF, FFFP, wet chemical) and CO2 and stainless-steel dry chemical extinguishers all operate on a 5-year hydrostatic cycle. See the reference table below for the full breakdown by type.

Here's the real operational challenge. Each extinguisher has a unique manufacture date, so the 6-year and 12-year schedules are staggered across your entire client inventory. Unlike monthly or annual inspections that you can batch-schedule for all units at a site, these maintenance intervals are unique to each individual extinguisher. You can't just show up every December and knock them all out at once.

Think about that hospital contract again. Of those 612 extinguishers, maybe 40 are due for 6-year internals this year. Another 25 need hydrostatic testing. Fifteen of those are water-based units on a 5-year cycle, and ten are dry chemical on a 12-year cycle. Tracking all of that in a spreadsheet is a recipe for missed deadlines and angry AHJ phone calls.

And then there's the swap problem. When an extinguisher gets discharged and you replace it with a spare, the records go stale immediately unless updated in real time. That spare might have a completely different manufacture date and service history. If nobody updates the tracking system, you've now got a unit that's past due for maintenance sitting in an active location, and nobody knows it.

NFPA 10 Quick-Reference: Inspection and Maintenance Intervals by Extinguisher Type

Based on NFPA 10, 2022 Edition (Chapters 7 and 8)

Extinguisher Type Monthly Visual Annual Maintenance Internal Exam Hydrostatic Test
Stored-Pressure Dry Chemical (ABC/BC) 30 days Yearly 6 years 12 years
Cartridge-Operated Dry Chemical 30 days Yearly Yearly* 12 years
Clean Agent (Halotron, FE-36, Halon) 30 days Yearly 6 years 12 years
Dry Powder (Class D) 30 days Yearly 6 years 12 years
Carbon Dioxide (CO2) 30 days Yearly** 5 years 5 years
Wet Chemical (Class K) 30 days Yearly 5 years 5 years
Water / Water Mist 30 days Yearly 5 years 5 years
AFFF / FFFP (Foam) 30 days Yearly 3 years 5 years
Stored-Pressure Loaded Stream / Antifreeze 30 days Yearly Yearly* 5 years
Dry Chemical (Stainless Steel Shell) 30 days Yearly 5 years 5 years
Non-Rechargeable (Disposable) 30 days Yearly N/A N/A (remove at 12 yrs)

*Cartridge-operated and loaded-stream/antifreeze extinguishers require internal examination during every annual maintenance.

**CO2 units also require an annual hose conductivity test (Section 7.4). No pressure gauge; fullness verified by weight only.

Note: The 6-year clock resets whenever recharging or hydrostatic testing is performed. Non-rechargeable extinguishers are removed from service at 12 years from manufacture date.

Tired of tracking all these intervals in spreadsheets?

Essential automates due date tracking for every extinguisher type and recalculates schedules when units get recharged or swapped. Book a free demo to see it in action.

What AHJs Actually Flag During Inspections

Knowing what AHJs look for helps you deliver better service and position yourself as the contractor who catches problems before the inspector does. The most common deficiencies found during AHJ inspections, based on fire marshal reports and industry data:

Obstructed access is the number one finding. Equipment, storage, and furniture blocking extinguishers shows up on almost every inspection report. Missing or expired inspection tags come in second, followed by gauges reading outside the operable range. Missing or broken safety seals and pins are next, then incorrect extinguisher type for the hazard (putting an ABC where a Class K should be, for example). Improper mounting height is another common one: the top of the extinguisher can't exceed 5 feet for units weighing 40 lbs or less, or 3.5 feet for units over 40 lbs.

Physical damage, illegible operating instructions, missing extinguishers, and overdue maintenance round out the list. An industry-cited figure suggests roughly 30% of fire extinguishers in service aren't in proper working condition. That's a compliance gap, but it's also a revenue opportunity for contractors who can document and fix those problems.

Real-World Scenario: Restaurant Chains and Class K Complications

Say you've got a 20-location restaurant chain as a client. Every kitchen needs a Class K wet chemical extinguisher within 30 feet travel distance of commercial cooking equipment. The dining areas and back offices still need standard ABC units at 75-foot spacing. And the kitchen hood suppression systems fall under NFPA 96 and NFPA 17A, requiring semi-annual inspection on top of the extinguisher work.

The critical timing difference that catches contractors off guard: those Class K wet chemical extinguishers operate on a 5-year hydrostatic and internal examination cycle, not the 12-year cycle for the ABC dry chemical units in the dining room. So you've got two completely different maintenance schedules running in parallel at every single location. Across 20 locations, that's 40 or more separate maintenance timelines to track, not counting the hood system inspections.

In states like Florida, a licensed fire extinguisher contractor must perform annual servicing and attach a state contractor's tag. Local AHJ requirements can layer additional rules on top of NFPA 10. You've got to know your jurisdiction.

CO2 Extinguishers: The Outlier You Can't Ignore

CO2 units have no pressure gauge. Fullness is verified by weighing only. They require an annual hose conductivity test per Section 7.4, and a non-conductive hose must be replaced immediately. CO2 cylinders are high-pressure vessels and get stamped per DOT requirements during hydrostatic testing.

If your client has server rooms, electrical rooms, or clean rooms, they probably have CO2 or clean agent extinguishers. These units need a different inspection workflow than your standard ABC dry chemical, and your technicians need to know the difference before they walk in the door.

Condemned Extinguishers: Know When to Kill It

An extinguisher must be condemned (stamped on the top, head, or shoulder) and removed from service permanently if it shows: evidence of soldering or welding repairs, damaged threads, pitting corrosion, fire damage, certain dent patterns, or wall thickness reduced by more than 10%. Non-rechargeable extinguishers don't get hydrostatically tested at all. They're simply removed from service at 12 years from the manufacture date.

The 2026 edition of NFPA 10 adds new disposal requirements for condemned non-DOT cylinders. If you're still servicing older inventory, it's worth getting ahead of that change now.

Stop Tracking Extinguishers Like It's 2005

If you're managing any serious extinguisher volume, you already know that paper tags and spreadsheets don't scale. The staggered maintenance intervals, the swap tracking, the varying hydrostatic cycles by type, the multi-site scheduling logistics: all of this gets exponentially harder with every new contract you sign.

Fire protection software built for this kind of work (platforms like Essential, for example) can automate due date tracking, generate deficiency quotes directly from field findings, and give your office staff a real-time view of what's due, what's overdue, and what needs to be condemned. Barcode scanning ties each unit to its full service history so your technicians aren't guessing in the field.

The contractors who are growing right now aren't the ones doing the most inspections. They're the ones who never miss a due date, never lose a service record, and never have to send a truck back to a site because someone didn't check the manufacture date before they left the shop.

If you want to see what that looks like in practice, the Essential team offers free demos with no commitment. It's worth 15 minutes to find out if you're leaving compliance gaps (and revenue) on the table.